banner
ACL

HM201-R Addressable Output Module

  • Home
  • HM201-R Addressable Output Module
project->image

HM201-R Addressable Output Module

The HM201-R can be installed in a single gang junction box directly behind the monitored unit. It is a addressable output module for installation on the 2-wire communication circuit and its location address is written inside the MCU’s EEPROM by the addressable programmer.

The HM201-R has two output modes can be selected:

1- Relay output mode: It contains a isolated set of form Ccontacts, which operate as a SPST switch. No supervision is provided for the notification appliance circuit.

2- Power output mode:It provides supervised monitoring ofwiring to load devices that require an external power supply to operate, such as horns, strobes, or Upon command from the control panel, the output module will disconnect the supervision and connect the external power supply across the load device.

The external power supply is always relay isolated from the communication loop, so that a trouble condition on the power supply will never interfere with the rest of the system.

Full analog measurement of the supervised wiring is transmitted back to the panel and can be used to detect impedance changes or other special test functions.

Description
Specificastions

Loop Voltage Range 16 to 28VDC , <450uA@28VDC
External power supply 16 to 32VDC
Maximum Alarm

 

Current

≤5mA @ 28 VDC
Operating Humidity

 

Range

10% to 93% Relative Humidity,

 

Non-condensing

Operating Voltage

 

Range

-10°C to 50°C
Relay contacts capacity 2Amp@30VDC
Power output capability 2Amp@30VDC
Dimensions(MM) 87*87*37(L*W*D)
Weight 81